Samsung MCM-D211UN Installation Manual page 39

Hide thumbs Also See for MCM-D211UN:

Advertisement

Option
SEG7
(When setting SEG3)
Standard for mode
Explanation
PAGE
change Cooling →
Heating mode
Remote
Controller
Display
Indication Details Indication
0
1
2
Indication
3
and Details
1
4
5
6
7
Option
SEG13
Damper minimum
Indication
0
1
2
Explanation
2
3
4
5
6
7
8
9
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 39
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 39
SEG8
SEG9
(When setting SEG3)
Compensation option for Long pipe or
Time required for mode
height difference between indoor units
change
Details
Indication
Details
Indication
1
0
5 min.
0
1.5
1
7 min.
2
2
9 min.
2.5
3
11 min.
3
4
13 min.
3.5
5
15 min.
2
4
6
20 min.
4.5
7
30 min.
SEG14
SEG15
Damper opening
output
minimum temperature
Details
Indication
Details
Indication
20 ℃
10%
0
0
(68 ℉)
15 ℃
20%
1
(59 ℉)
10 ℃
30%
2
2
(50 ℉)
5 ℃
40%
3
3
(41 ℉)
0 ℃
50%
4
4
(32 ℉)
-5 ℃
60%
5
5
(23 ℉)
-10 ℃
70%
6
6
(14 ℉)
-15 ℃
80%
7
(5 ℉)
90%
-20 ℃
8
8
(-4 ℉)
100%
SEG10
Details
Use default value
1)
1) Height difference
is more than
30 m (98.4ft) or
1
2)
2) Distance
is longer than 100 m
(328. 1 ft)
1)
1) Height difference
is 15~30 m
(49.2~98.4ft) or
2) Distance
2)
is 15~110 m
(49.2~360. 9 ft)
SEG16
Control Method by using
Damper control setting
Details
Damper
Damper
Damper
Indication
operation
output
output
(Fan mode)
(Cooling)
(Heating)
Damper Disuse
1
ON
Variable Variable
0
ON
Fixed
Variable
1
ON
Variable
Fixed
ON
Fixed
Fixed
OFF
Variable Variable
2
OFF
Fixed
Variable
7
OFF
Variable
Fixed
F
OFF
Fixed
Fixed
SEG11
SEG12
Criterion enthalpy
Details
Indication
0
35 kJ/kg (15.0 Btu/lb)
1
40 kJ/kg (17.2 Btu/lb)
2
45 kJ/kg (19.3 Btu/lb)
3
50 kJ/kg (21.5 Btu/lb)
4
55 kJ/kg (23.6 Btu/lb)
5
60 kJ/kg (25.8 Btu/lb)
SEG17
SEG18
-
simple BMS
Details
Set temp.
Details
Indication
Delay time for
for heater
heater On
On/Off
At the
same time
0
No delay
as thermo
on
At the
Room
same time
1
10 minutes
Temerature
as thermo
on
At the
same time
2
20 minutes
as thermo
on
1.5 °C
3
No delay
(2.7 °F)
1.5 °C
4
10 minutes
(2.7 °F)
Discharge
Temperature
1.5 °C
5
20 minutes
(2.7 °F)
3.0 °C
6
No delay
(5.4 °F)
3.0 °C
7
10 minutes
Target
(5.4 °F)
Pressure
3.0 °C
(Cooling Mode
8
20 minutes
(5.4 °F)
: Evaporating
Pressure
4.5 °C
9
No delay
Heating Mode
(8. 1 °F)
: Condensing
4.5 °C
Pressure)
A
10 minutes
(8. 1 °F)
4.5 °C
B
20 minutes
(8. 1 °F)
Only Operation
6.0 °C
C
No delay
Mode Control
(10.8 °F)
(Temperature/
6.0 °C
Pressure Control
D
10 minutes
(10.8 °F)
Not applied)
6.0 °C
E
20 minutes
(10.8 °F)
2023-01-13 오전 11:35:18
2023-01-13 오전 11:35:18
39