Installing a Universal Comm. Kit
Simple BMS
Simple BMS setting
▶ Simple BMS can control Room temperature or Discharge temperature by setting SEG17 of 05 series
Installation option.
‐ For controlling Room temperature : SEG17 of 05 series Installation option → 0
‐ For controlling Discharge temperature : SEG17 of 05 series Installation option → 1
‐ For controlling Target Pressure : SEG17 of 05 series Installation option → 2
▶ Discharge temperature can be set by DMS.
▶ Simple BMS control is not influenced by DMS's restrictions on operation mode, set temperature or remote
controller usage.
▶ If you want to set Room temperature or Discharge temperature by using Simple BMS, setting Buzzer
control option as "Disuse buzzer" is recommended.
Circuit diagram of Simple BMS
COM
HP
CO
AV
OV
Shielding
• Hysteresis is applied to the end of voltage range in order to stabilize the analog input.
The amount of Hysteresis
CAUTION
‐ Room temperature setting: 0.15 V
‐ Discharge temperature setting: 0.08 V
10
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 10
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 10
Ex) setting up 22℃ (71.6℉) (Simple BMS : Room temperature setting)
[Voltage]
decreasing
temperature
4.8V
4.65V
4.6V
4.4V
4.25V
The areas of 23℃ (73.4℉)
4.95V
The areas of 22℃ (71.6℉)
4.55V
The areas of 21℃ (69.8℉)