Operational Voltage range against Setting temperature
▶ Room temperature setting (05 Series Install Option Seg17=0)
Simple BMS Voltage Range
10.0 V ~ 9.6 V
9.6 V ~ 9.2 V
9.2 V ~ 8.8 V
8.8 V ~ 8.4 V
8.4 V ~ 8.0 V
8.0 V ~ 7.6 V
7.6 V ~ 7.2 V
7.2 V ~ 6.8 V
6.8 V ~ 6.4 V
6.4 V ~ 6.0 V
6.0 V ~ 5.6 V
5.6 V ~ 5.2 V
5.2 V ~ 4.8 V
4.8 V ~ 4.4 V
4.4 V ~ 4.0 V
4.0 V ~ 3.6 V
3.6 V ~ 3.2 V
3.2 V ~ 2.8 V
2.8 V ~ 2.4 V
2.4 V ~ 2.0 V
2.0 V ~ 1.6 V
1.6 V ~ 1.2 V
1.2 V ~ 0.8 V
0.8 V ~ 0.4 V
0.4 V ~ 0.0 V
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 11
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 11
Set Temperature
Heating
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
29 ˚C (84.2 ℉)
28 ˚C (82.4 ℉)
27 ˚C (80.6 ℉)
26 ˚C (78.8 ℉)
25 ˚C (77.0 ℉)
24 ˚C (75.2 ℉)
23 ˚C (73.4 ℉)
22 ˚C (71.6 ℉)
21 ˚C (69.8 ℉)
20 ˚C (68.0 ℉)
19 ˚C (66.2 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
Cooling
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
30 ˚C (86.0 ℉)
29 ˚C (84.2 ℉)
28 ˚C (82.4 ℉)
27 ˚C (80.6 ℉)
26 ˚C (78.8 ℉)
25 ˚C (77.0 ℉)
24 ˚C (75.2 ℉)
23 ˚C (73.4 ℉)
22 ˚C (71.6 ℉)
21 ˚C (69.8 ℉)
20 ˚C (68.0 ℉)
19 ˚C (66.2 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)
18 ˚C (64.4 ℉)