Option
SEG19
Explanation
PAGE
Remote
Controller
Display
Indication Details
Indication and
Details
3
Minimizing fan operation when thermostat is off
(*1)
‐ Fan operates for 20 seconds at an interval of 5 minutes in Heat mode.
‐ Fan stops when thermostat is off in Cool mode.
‐ Make sure to connect the wired remote controller or the external room temperature sensor if you use the
function of external room temperature sensor or minimizing fan operation. (In order to implement the
functions the option of using temperature sensor inside the wired remote controller must be set. Refer to
the installation manual of the wired remote controller.
1: Fan is turned on continually when the hot water heater is turned on,
(*2)
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor
unit and fix it as Cool mode.
4: Fan speed is high mode continually when the hot water heater is turned on
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external
(*3)
contact control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor
unit and fix it as Cool mode
4: The cooling operation status is displayed.
5: Fan speed stays in the high mode continuously when the hot water heater is turned on.
Thermal ON contact signal(B17/B18) is related to fan operation : when the fan is stopped, the contact
(*4)
output for Thermo ON is not generated (e.g. defrosting operation).
Thermal ON contact signal(B17/B18) is not related to fan operation : Regardless of Fan ON/OFF, the contact
output is generated with Thermo ON.
Cooling thermal ON contact(B13/B14) includes dehumidification thermal ON : The contact output is
generated with cooling or dehumidification Thermo ON.
Cooling thermal ON contact(B13/B14) don't include dehumidification thermal ON : The contact output is
generated with cooling Thermo ON.
When Cool or Dry mode is off. The indoor fan operate in setting minutes.
(*5)
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 37
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 37
SEG20
SEG21
Offset of compensation for
heating installation
Indication
Details
0
Default
1
2°C (3.6°F)
2
5°C (9.0°F)
SEG22
SEG23
Forced FAN Operation for
Oil return/EEV step of
stopped defrost mode
Heating and Cooling
Details
Indication Details Indication
Cooling Fan
Heating Fan
Setting
0
Disuse
Use (Fan: User
Default
1
Disuse
0
value
2
Disuse
Use (Fan: High)
3
Disuse
Use (Fan: Low)
Use (Fan: User
4
setting)
Use (Fan: User
Use (Fan: User
5
setting)
Use (Fan: User
6
Use (Fan: High)
setting)
Use (Fan: User
7
Use (Fan: Low)
setting)
Noise
8
Use (Fan: High)
1
decreasing
Use (Fan: User
9
Use (Fan: High)
setting
A
Use (Fan: High) Use (Fan: High)
B
Use (Fan: High) Use (Fan: Low)
C
Use (Fan: Low)
Use (Fan: User
D
Use (Fan: Low)
E
Use (Fan: Low) Use (Fan: High)
F
Use (Fan: Low) Use (Fan: Low)
SEG24
Indoor unit type
Details
Indication
Model
Enthalpy
Fan
Setting
type
S/S
Motor
Disuse
0
Common Disuse Fixed
setting)
1
DOAS Disuse Fixed
Disuse
2
Common Use
Fixed
setting)
3
DOAS
Use
Fixed
Disuse
4
Common Disuse Variable
setting)
5
DOAS Disuse Variable
Disuse
6
Common Use Variable
setting)
7
DOAS
Use Variable
37