Setting the installation option of an Universal Comm. Kit (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
‐ When the Universal Comm. Kit is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the Universal Comm. Kit PBA.
3. Set the installation option of an Universal Comm. Kit according to installation conditions.
‐ The default setting of an Universal Comm. Kit installation option (02 series) is ''020010-100000-200000-300000'' .
‐ The default setting of an Universal Comm. Kit installation option (05 series) is ''050000-100003-224000-340000'' .
4. Set the Universal Comm. Kit option with a remote controller.
■ 02 series installation option
SEG1
0
SEG7
1
SEG13
2
External control
SEG19
3
▶ SEG5 central control option is basically set as 1 (Use), so you don't need to set the central control option
additionally. When you exclude the indoor unit control from central control, change the setting as 0(Disuse).
▶ When you set the value other than the SEG setting values, it will be set as "0".
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication
Indication and
Details
0
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 35
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 35
SEG2
SEG3
2
Evaporator Drying
SEG8
SEG9
-
Hot water heater
SEG14
SEG15
External control output
SEG20
SE21
Compensation of
-
heating setting
(
5)
SEG2
SEG3
*
MODE
Evaporator Drying
Minimizing fan operation when thermostat is off
0
Disuse
Use
2
(*1)
(5min)
2
Use
4
(*1)
(10min)
Use
6
(*1)
(30min)
SEG4
External room
temperature sensor/
Central control
Minimizing fan operation
when thermostat is off
SEG10
EEV Step when heating
Contact signal
SEG16
-
SEG22
Oil return/EEV step of
Forced FAN Operation
stopped defrost mode
for Heating and Cooling
(*1)
SEG4
Use of external room temperature sensor/
Details
Use of External
Minimizing fan
room temperature
operation when
sensor
thermostat is off
0
Disuse
Disuse
1
Use
Disuse
2
Disuse
Heating Use
3
Use
Heating Use
4
Disuse
Cooling Use
5
Use
Cooling Use
6
Disuse
All Use
7
Use
All Use
8
Disuse
Use (Cooling Ultra Low Fan )
9
Use
Use (Cooling Ultra Low Fan )
Use (Heating / Cooling Ultra
A
Disuse
Low Fan )
Use (Heating / Cooling Ultra
B
Use
Low Fan )
SEG5
SEG6
-
SEG11
SEG12
-
stops
SEG17
SEG18
Buzzer
-
SEG23
SEG24
Indoor unit type
SEG5
SEG6
Use of central control FAN RPM compensation
Indication Details
0
Disuse
1
Use
35