Wire
saddle
※ EEV connector connection should be fixed to the wire saddle as shown in the image.
• Be careful when setting the number of the indoor unit installation with an outdoor unit.
• When setting Universal Comm. Kit capacity, refer to the SEG 20 of Installation option 05 series on
CAUTION
page 40.
• Regardless of the Universal Comm. Kit capacity setting, one indoor unit will be recognized.
[EEV Models and Quantities for each Capacity]
▶ SEG 20 of the installation option 05 series
Rated Capacity
Disaply
(Btu/h)
0
12k
1
12k
2
24k
3
36k
4
48k
5
60k
6
72k
7
96k
8
144k
9
192k
A
240k
B
288k
C
336k
D
384k
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 19
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 19
EEV-1
EEV-2
EEV-3
EEV-4
Capacity Range
Heat Exchanger
(Btu/h)
Volume(in³)
7k≤ capacity ≤18k
28≤ volume ≤71
7k≤ capacity ≤18k
28≤ volume ≤71
18k< capacity ≤30k
71< volume ≤118
30k< capacity ≤42k
118< volume ≤165
42k< capacity ≤60k
165< volume ≤236
60k< capacity ≤72k
236< volume ≤283
72k< capacity ≤96k
283< volume ≤378
96k< capacity ≤144k
378< volume ≤566
144k< capacity ≤192k
566< volume ≤755
192k< capacity ≤240k
755< volume ≤944
240k< capacity ≤288k
944< volume ≤1133
288k< capacity ≤336k
1133< volume ≤1322
336k< capacity ≤384k
1322< volume ≤1510
384k< capacity ≤480k
1510< volume ≤1725
Assy EEV
Number of EEVs
MXD-A24K100E
1
MXD-A24K100E
1
MXD-A32K100E
1
MXD-A40K100E
1
MXD-A40K100E
1
MXD-A64K100E
1
MXD-A64K100E
1
MXD-A64K100E
2
MXD-A64K100E
2
MXD-A64K100E
3
MXD-A64K100E
3
MXD-A64K100E
4
MXD-A64K100E
4
MXD-A64K100E
4