Samsung MCM-D211UN Installation Manual page 26

Hide thumbs Also See for MCM-D211UN:

Advertisement

Installing a Universal Comm. Kit
2. Enthalpy sensor control
1) Operate the product after comparison between the intake enthapy of indoor unit and reference
enthalpy.
‐ Reference enthalpy (installation option code; selectable according to the site)
‐ Cooling Thermo OFF & (enthalpy > reference enthalpy): Cooling T-ON
2) The reference enthalpy for cooling T-ON can be set depending on the site.
‐ If it is required to keep a lower humidity, decrease the reference enthapy. For a higher humidity,
increase the reference enthalpy.
‐ Can set in the 05 series installation option SEG12 (reference enthalpy default: 50 kJ/kg (21.5 Btu/lb).
3) Comparison of cooling operations depending on the enthalpy sensor availability
Intake Temp.
B or above
Below B
3. Wiring example
26
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 26
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 26
Enthalpy Sensor Not Applicable
: Thermo ON
: Thermo OFF
: Thermo OFF
[Psychometric Chart]
Reference
Enthalpy
A
3
1
B
Room Temperature Setting
Enthalpy Sensor Applicable
: Thermo ON
: Thermo OFF
: Thermo ON
Absolute
Humidity
2
Power
(12 to 40 Vdc)
(Field supplied)
(COM)
(+)
(+)
Enthalpy
(Field supplied)
Sensor
(-)
COM
(+)
Enthalpy
2023-01-13 오전 11:35:13
2023-01-13 오전 11:35:13