Setting an indoor unit type
In the 02 series installation option SEG 24, configure the settings depending on the indoor unit.
No.
Item
1
Indoor Unit Type
2
Fan Motor Type
3
Enthalpy Sensor
No.
Control logic
1
Preventing cold wind
Discharge air temperature control in
2
HR mode
3
Thermo OFF decision
Operation restriction depending on
4
outdoor temperature
Fan Motor
In the installation option SEG 24, set the fan motor type.
1. In case of the fixed type setting
▶ Connect the PBA Fan out to the motor control signal.
▶ While the contact output for fan out is generated in contact closed, the contact output for fan out is not
generated in contact open.
2. In case of the variable type setting
▶ Connect the PBA H/M/L to the motor control signal.
▶ Depending on the fan out (H/M/L), the corresponding contact output is generated.
• Do not power the motor with the fan speed output contacts. If it is not the motor control signal
but the motor drive power, be sure to connect an external relay.
CAUTION
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 21
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 21
Type
Description
Circulates indoor air in
Common
and out of indoor unit
Dedicated Outdoor Air
Provides and conditions
System (DOAS)
100% outside air
Cannot change the Fan
Fixed
speed.
Can change the Fan
Variable
speed to H, M, and L.
Does not use the
Disuse
enthalpy sensor.
Uses the enthalpy
use
sensor.
'Common' setting
Fan off when average evaporator
temperatrue is below 28℃ (82.4℉)
impossible
depending on room temperature only
use
Control Item
Refer to the below table
H/M/L setting and display are not possible
on the controller.
H/M/L setting and display are possible on
the controller.
When the enthalpy sensor value is greater
than the reference value even though the
current temperature satisfies the setting
for cooling, it performs cooling operation.
Installation option 02 series SEG 24
Fan off when average evaporator
temperatrue is below 5℃ (41℉)
Possible (Main cooling only)
While outdoor unit keeps main
cooling mode, only heating unit
can control discharge temperature
Heating unit controls EEV step
depending on target discharge
temperature
depending on room temperature
or discharge temperature
disuse
'DOAS' setting
21
2023-01-13 오전 11:35:12
2023-01-13 오전 11:35:12