Samsung MCM-D211UN Installation Manual page 20

Hide thumbs Also See for MCM-D211UN:

Advertisement

Installing a Universal Comm. Kit
Installing IN/OUT sensor
1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200 mm (7.87") after the header of Indoor unit heat exchanger as shown in
the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by airflow.
4. Install the ROOM temperature sensor on the RA (Return Air) path of Indoor unit.
※ In case of DOAS, install ROOM temperature sensor and enthalpy sensor (optional) on the OA (Outdoor Air)
path in front of indoor unit heat exchanger
Selecting the location of EVA_IN/OUT sensor
Header
Example of ROOM temperature sensor installation
Return air
Exhaust air
Location of room temperature sensor
• In principle, the sensor holder of EVA IN/OUT sensor should be welded at the designated place and
then the EVA IN/OUT sensor should be fixed with a clip.
NOTE
• EVA IN/OUT sensor should be installed at the place where temperature of the heat exchanger inlet
or outlet can be measured accurately.
20
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 20
DB68-06643A-03_IM_ACC UCK Kit_AA_EN.indd 20
※ Refrigerant flow
Distributor
1 EVA IN sensor
2 EVA OUT sensor
Supply air
Outdoor air
Cool mode
Heat mode