Delta Amplon Series User Manual page 22

Hide thumbs Also See for Amplon Series:
Table of Contents

Advertisement

06: Bypass enable/ disable when the UPS is off
Parameter 3: Enable or disable bypass function. You may choose the
following two options.
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable
low voltage point for bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
Amplon N Gen3 Series
1 9