2.4. Terminal Resistor Notes for CAN Interface

In order to minimize the effects of reflection on the CAN Bus, the bus must be terminated using a
terminal resistor at each end. According to the specifications given in ISO 11898-2, each terminal
resistor should be 120Ω(or between 96Ω and 144Ω). The bus topology and the positions of these
terminal resistors are shown below.
The ECAN-240-FD module includes two CAN ports and terminal resistors are provided for each
CAN port. The terminal resistor can be enabled or disabled via the terminator DIP-switches as
illustrated in following figure.
As indicated in the figure, when the DIP-switch is in the OFF position, the terminal resistor
function is disabled. Similarly, when the DIP-switch is in the ON position, the terminal resistor
function is enabled.