Mounting; General Instructions - Vega VEGACAP 27 Operating Instructions Manual

Capacitive rod electrode for level detection relay (dpdt)
Hide thumbs Also See for VEGACAP 27:
Table of Contents

Advertisement

Process conditions
Suitability for the ambient
conditions
Switching point
Welding work
Handling
Moisture
VEGACAP 27 • Relay (DPDT)
4

Mounting

4.1

General instructions

Note:
For safety reasons, the instrument must only be operated within the
permissible process conditions. You can find detailed information on
the process conditions in chapter " Technical data" of the operating
instructions or on the type label.
Hence make sure before mounting that all parts of the instrument ex-
posed to the process are suitable for the existing process conditions.
These are mainly:
Active measuring component
Process fitting
Process seal
Process conditions in particular are:
Process pressure
Process temperature
Chemical properties of the medium
Abrasion and mechanical influences
The instrument is suitable for standard and extended ambient condi-
tions acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1. It can be used
indoors as well as outdoors.
In general the level switch can be mounted in any position. The instru-
ment must be mounted in such a way that the probe is at the height of
the requested switching point.
Before beginning the welding work, remove the electronics module
from the sensor. By doing this, you avoid damage to the electronics
through inductive coupling.
Ground the probe before welding directly on the rod or cable.
With threaded versions, the housing must not be used to screw in the
instrument! Applying tightening forces on the housing can damage its
internal parts.
Use the hexagon for screwing in.
Use the recommended cables (see chapter " Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable gland. Rain and condensation water can thus drain off. This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g. through cleaning processes) or
on cooled or heated vessels.
4 Mounting
9