Vega VEGACAP 27 Operating Instructions Manual page 13

Capacitive rod electrode for level detection relay (dpdt)
Hide thumbs Also See for VEGACAP 27:
Table of Contents

Advertisement

Connection to a PLC
VEGACAP 27 • Relay (DPDT)
+
L1
1
Fig. 5: Wiring plan
1
Relay output
2
Relay output
3
Voltage supply
If inductive loads or stronger currents are switched through, the gold
plating on the relay contact surface will be permanently damaged.
The contact is then no longer suitable for switching low-voltage
circuits.
Inductive loads also result from the connection to a PLC input or
output and/or in combination with long cables. It is imperative that you
take measures to extinguish sparks to protect the relay contact (e.g. Z
diode) or use an electronic version with transistor output.
5 Connecting to power supply
N
2
3
4
5
6
7
8
1
2
3
13

Advertisement

Table of Contents
loading

Table of Contents