120
Diagnostics
Pos : 46 /All e Seri en (Allgemei ne Module)/Ü berschriften/N eue Ü berschriften/Ebene 1Di agnos e - Ü bersc hrift 1 @ 4\mod_1240831069471_21.doc x @ 31372 @ 1 @ 1
14
Diagnostics
Pos : 47.1 /All e Seri en ( Allgemei ne Module)/Ü bers chriften/Ebene 2LED- Signalisi erung - Ü bersc hrift 2 @ 4\mod_1240831118032_21.doc x @ 31375 @ 2 @ 1
14.1
LED Signaling
Pos : 47.2 /Serie 767 (WAGO-SPEED WAY)/Di agnose/Fel dbus koppl er/Diag nose, Ei nleitung xxxxxx @ 7\mod_1269243989708_21.doc x @ 53636 @ @ 1
For the local diagnostic, the fieldbus coupler contains various LEDs that display
the operating state of both the fieldbus coupler and the S-BUS. This information
can also be displayed with WAGOframe. For more information, see section
"Readout of Blink Codes using WAGO DTMs".
Pos : 47.3 /Serie 767 (WAGO-SPEED WAY)/Di agnose/Fel dbus koppl er/Statusmel dungen Einl eitung 767-1501 @ 8\mod_1281074751693_21.doc x @ 62540 @ 2 @ 1
14.2
CANopen Status Messages
The following table lists the CANopen status messages that are signalized by the
LEDs (21) on the fieldbus coupler. Information regarding remedies of certain
causes is also provided.
Pos : 47.4 /Serie 767 (WAGO-SPEED WAY)/Di agnose/Fel dbus koppl er/Statusmel dungen Bild 767- 1501 @ 8\mod_1281086183150_21.doc x @ 62594 @ @ 1
21
Figure 46: LEDs which display status messages
Pos : 47.5 /Serie 767 (WAGO-SPEED WAY)/Di agnose/Fel dbus koppl er/Statusmel dungen T abelle 767-1501 @ 8\mod_1281075737002_21.doc x @ 62544 @ @ 1
Table 64: Status messages of the RX and TX LEDs
LED
RX
TX
Color
Cause
Red
The CAN receiver buffer is
full. Data loss can be
anticipated.
Red
The CAN sending buffer is
full. Data loss can be
anticipated.
WAGO-SPEEDWAY 767
767-1501 FC CANopen 8DI 24V DC
Remedy/information
Check the configuration of the
CAN bus.
Downsize the COB ID of the
TxPDO.
Check the configuration of the
CAN bus.
Send fewer PDOs per time unit
to the fieldbus coupler.
Manual