8. Offline configuration

Using the configuration cable to connect to the sensor as below picture.
Serial port configuration on computer: 9600 baud, None parity, 1 stop bit.
Reading data by Function 3.
Writing data by Function 16.
During connection with Modbus configuration tool, the Sigfox node will send all data in realtime: Battery, Battery level,
Vref, Button status, reed switch status, PCB temperature, Measured value, alarm status.
Step to configure & check data:
NOTE:
The Modbus configuration can be done in the first
finish the configuration, user need to reset the power of Sigfox node again, by removing battery in at least 15s.
3
16
1
3
16
2
3
16
2
3
16
2
3
16
2
3
16
2
3
16
2
TX_POWER
20
CONSTANT_A
1
CONSTANT_B
0
HIGH_CUT
1E+09
LOW_CUT
-1E+09
SENSOR_BOOT_TIME
200
SYSTEM_SENSITIVITY
11
60s
after power up the Sigfox node. After 60s, if user can not
Read /
RF Tx
int16
Write
power
Constant a
Read /
for scaling
float
Write
measured
value
Constant b
Read /
for scaling
float
Write
measured
value
High cut
Read /
value for
float
Write
calculated
value
Low cut
Read /
value for
float
Write
calculated
value
Boot time
of
Read /
sensor/input,
uint32
Write
in ms
The
sensitivity
Read /
float
of the
Write
circuit
(mV/ppm)