2. Introduction WS433-O2 is the Wireless Ambient Oxygen Sensor, it utilises galvanic cell type oxygen sensor which provides a linear output voltage signal relative to percent oxygen present in a particular atmosphere. The sensor features no position dependency, excellent chemical durability, and it is not influenced by CO. The wireless portion is Sub-GHz technology from Texas Instruments allows long range transmission at ultra-low power consumption.
3. Specification SENSOR SPECIFICATION : Measuring range 0-30% O2 Accuracy 0.25% O2 Resolution 0.01 Working Pressure 507 hPa - 1520 hPa Working Temperature -10 .. + 50oC Working Humidity 0-99%, non-condensation Response time ≤15s Life expectancy at 20 ̊ C in normal air approx.
5. Operation Principle 5.1 Process of measurement When the sensor sampling time interval is reached, For example minutes, the node will wake up and switch ON the power supply to supply the energy to external sensor to start the measurement. Depends on the type and characteristic of external sensor, the sensor will take a certain time to finish the measurement.
Page 5
(add up to 40 nodes) . After 5 minutes Enb_auto_add_sensors will automatically = 0. Memmap resgisters You can download Modbus Memmap of WS433-CL with the following link: https://filerun.daviteq.com/wl/?id=WBbGm89AToHWyvIyMOc780N1KmjfUr3Y 5.2.2 Add sensor node into WS433-CL-04 (1) through intermediate WS433-CL-04 (2) and Modbus In case the sensor need to be added to WS433-CL-04 (1) has been installed in a high position, the sensor cannot be brought close to WS433-CL-04 (1).
5.3 Button Function Open the cover of sensor then use the push button to set the data transfer speed for the first 30 seconds when the battery is first installed, after 30 seconds the push button function does not work. Press and hold the button for 2 seconds =>...
Page 7
Num of Node will indicate the number of nodes managed by WS433-CL. Every time a node is added, the Num of Node will increase by 1. Every time a node is deleted, the Num of Node is reduced by 1. Writing Num of Node = 0 will delete all 40 node ids to 0.
Page 8
Step 2: Open Modbus tool on PC You can download Daviteq Modbus Configuration Tool with the following link: https://filerun.daviteq.com/wl/?id=qK0PGNbY1g1fuxTqbFW9SXtEvCw7bpc6 Template File: https://filerun.daviteq.com/wl/?id=ItFaeQgtCmXN98J7GaPdeZvKK5eS1Dd1 How to use the Modbus configuration software Unzip file and run file application "Daviteq Modbus Configuration Tool Version"...
Page 9
Step 3: Configure parameters of the sensor. Memmap resgisters You can download Modbus Memmap of WS433-CL with the following link: https://filerun.daviteq.com/wl/?id=BKEaUzdArkoc0Hc7nfpRShdPVToVrqQZ In the memmap file, refer to the Memmap of WS433-AI sheet to configure the sensor's operating parameters accordingly. The reference memmap addresses are based on the order of the sensors added in the Memmap file...
Page 10
Value from Analog input Analog sensor value 1 of (Oxygen). sensor float Read This value Node (parameter parameter 1 of a wireless sensor node Value of Same as parameter float Read parameter 2 of sensor Node 0-9: Interval Data status updated 0-9, 99 byte...
NOTE: Integrated WS433-CL / iConnector Coordinator The coordinator must be placed at least 4 meters above the ground and the WS433-O2 clearly visible. 6.2 First setup Please follow the steps described below...
Page 12
Step 2: Remove the tape on the sensor's filter DO NOT TOUCH WITH YOUR HANDS OR CONTAMINATING THE SENSOR FILTER Step 3: Carefully reattach the sensor protective cover...
Page 13
Now the sensor is ready to use 6.3 Dimensions Unit: mm...
6.4 Battery installation Steps for battery installation: Step 1: Using Philips screw driver to unscrew M2 screw at the side of housing. Step 2: Pull out the cover then insert the AA 1.5VDC battery, please take note the poles of the battery. ATTENTION: Because of O-ring, it requires to have much pulling force at the beginning, therefore please do it carefully to avoid the damage of circuit board which is very thin (1.00mm);...
No.11 Street 2G, Nam Hung Vuong Res., An Lac Ward, Binh Tan Dist., Ho Chi Minh City, Vietnam. Templogger Pty Ltd Tel: +84-28-6268.2523/4 (ext.122) Tel: 1800 LOGGER Email: info@daviteq.com | www.daviteq.com Email: contact@templogger.net Revision #5 Created Thu, Aug 5, 2021 8:41 AM by Kiệt Anh Nguyễn Updated Fri, Aug 6, 2021 8:26 AM by Kiệt Anh Nguyễn...