6.6 Configuration Parameters

Category
Parameter
DEVICE
LED_BUZZER_ENABLE
DEVICE
DEVICE_RESET
DEVICE
TX_REPEAT
HEARTBEAT
HEARTBEAT_PERIOD
NH3
NH3_ENABLE
NH3_MEASURE_PERIOD
NH3
6
7
8
9
10
11
12
13
14
15
Description
Possible values
Flag to enable/disable
0b0 = false, LEDs are
LED and Buzzer
OFF
interactions for action
0b1 = true, LEDs are
not triggered by the
ON
button.
Once this parameter
is set, the device
0b1010 = 0xA =
shall restart once
Force device reset
after having received
others = do nothing
the DL.
0b0 = 1 frames
Number of Sigfox
0b1 = 3 frames
frames
0b000 = every 1h
0b001 = every 6h
0b010 = every 12h
0b011 = every 24h (1
day)
0b100 = every 48h (2
Period of time to send
day)
HEARTBEAT event
0b101 = every 72h (3
day)
0b110 = every 120h
(5 day)
0b111 = every 240h
(10 day)
0b0 = false, NH3
sensing is disabled
Enable NH3 sensing
0b1 = true, NH3
sensing is enabled
0b0000 = every 1s
0b0001 = every 2s
0b0010 = every 5s
0b0011 = every 10s
0b0100 = every 20s
0b0101 = every 30s
0b0110 = every 1min
0b0111 = every 2min
Interval of time
0b1000 = every 5min
between two
0b1001 = every
consecutive NH3
10min
values are acquired
0b1010 = every
20min
0b1011 = every
30min
0b1100 = every 1h
0b1101 = every 2h
0b1110 = every 3h
0b1111 = every 6h
Length
Default value
(in bits)
0b0 = false
1
others = do nothing
4
0b0 = 1 frames
1
0b100= every 48h (2
3
days)
0b1 = true
1
0b0010 = every 5s
4