fan should be located no more than 120 ft from the furthest heater in the zone. Sufficient air
supply must be provided.
Exhauster Capacity:
USA: Natural or mechanical means shall be provided to supply and exhaust at least
3
4ft
/min/1000Btuh [0.38m
min/1000Btuh [0..43m
terlock to a dedicated exhaust fan. Consult your local code and ANSI Z223.1 latest
edition for all venting requirements and practices.
Canada: It is required that the heater[s] be electrically interlocked to dedicated exhaust
fan[s] by means of an Air Proving Switch. Exhaust fan[s] must be sized to create 300
cfm [8.5 cu m/min] exhaust for every 100,000 Btuh [30 kW] or any portion thereof of
total input of installed equipment. Provide combustion and ventilation air supply com-
patible with exhaust volume . Consult the latest edition of CSA.B149.1 Section 7.22.
15. REMOTE CONTROL OPTION [Single-Stage Models ONLY]
Patio Heaters can be operated using a portable Remote Control Option:
JP-1236-RK Remote Receiver Kit [field installed in the heater]
JP-1236-HS Remote 4-Button Handset Transmitter
The Handset Transmitter is the master component for system setup and operation.
It is recommended to have a backup/spare "twin" handset transmitter in case one is
misplaced
Handsets plug together to "twin" a backup handset with the same codes as master
In the event of any concern for breach of control security [lost handset], master
codes can easily be changed in existing handset[s] on site
Unique random signal codes ensures no interference with any neighboring systems
Optional : JP-1236-KT Wireless Keypad Transmitter [wall mounted at patio]
Control up to four heater zones using unique PIN's
Requires a Handset Transmitter as master code controller
Quick Setup instruction sheets accompany the Remote Receiver Kit and the Handset
Transmitter for installation and programming of the system.
Layout and Control:
Each heater requires its own receiver [JP-1236-RK]
Each handset transmitter has 4 channels and can control up to 4 individual heat zones
Multiple receivers can be programmed to one common transmitter channel [button]
Multiple heaters can be simultaneously activated in one heating zone with one
transmitter button
If more than 4 heating zones are required, then more than one master handset transmitter
is required; two master handsets can control up to 8 heating zones,
3
/min/kW] Natural Gas input of installed heaters [4.5ft
3
/min/kW] Propane input]. Some local codes may require an in-
27
3
/
2100 / IO-100 Manual
IM110107
RD: AUG 2021
R.L. 11A