3 Troubleshooting
3-1
Troubleshooting during Firmware Up-
date
This section describes how to troubleshoot problems that occur during firmware update.
Check the operation status indicators, and implement corrections and measures.
Indicator
RUN
Not lit
ERROR
Lit
NET RUN
---
NET ERR
---
LINK/ACT
---
RUN
Flashing
ERROR
Lit
NET RUN
---
NET ERR
---
LINK/ACT
---
RUN
Lit
ERROR
Flashing
NET RUN
NET RUN,
NET ERR
NET ERR,
LINK/ACT
and
LINK/ACT
are all not lit,
or either one
is lit.
RUN
Flashing
ERROR
Flashing
NET RUN
Not lit
NET ERR
Not lit
LINK/ACT
Not lit
RUN
Flashing
ERROR
Not lit
NET RUN
---
NET ERR
---
LINK/ACT
---
*1.
This applies to the NX701 CPU Unit, NX102 CPU Unit, and NX1P2 CPU Unit.
*2.
This applies to the NJ Series.
3-2
Cause of error
The Memory Card for updating firmware
is not inserted.
The Memory Card for updating firmware
is not recognized.
The DIP switch settings are not correct.
The model number of the CPU Unit is not
applicable for the Memory Card for updat-
ing firmware.
Firmware that is applicable to the hard-
ware revision of the CPU Unit to be up-
dated is not included in the Memory Card
for updating firmware.
It is not a Memory Card for updating firm-
ware.
Updated the firmware of the CPU Unit that
does not have F1 marked near the DIP
*1
switch.
The contents of Memory Card for updat-
ing firmware are broken.
The required files in the Memory Card for
updating firmware are missing.
Failed to rewrite the firmware of the CPU
Unit.
Malfunction of the CPU Unit.
The Firmware update prohibition for the
CPU Unit is set to Use.
The DIP switch settings are not correct.
Updated the firmware of the CPU Unit
that does not have F1 marked near the
*2
DIP switch.
NJ/NX-series Firmware Update Instruction with Memory Cards (P161)
Correction
Insert the Memory Card for updating firm-
ware and perform the firmware update.
The SD Memory Cards that comply with
the SDXC standard cannot be used.
Check the DIP switch settings and set
them correctly.
Use a Memory Card for updating firmware
that is compatible with the CPU Unit to
which the firmware update is applied.
To update the firmware of a CPU Unit that
does not have F1 marked near the DIP
switch, contact your OMRON representa-
tive.
The Memory Card for updating firmware
is broken.
Use the Firmware Updater Writer to cre-
ate a Memory Card for updating firmware
again, and then perform the firmware up-
date.
If the above corrections do not solve the
problem, replace the CPU Unit.
Set the Firmware update prohibition for
the CPU Unit to Do not use, and then per-
form the firmware update.
Check the DIP switch settings and set
them correctly.
To update the firmware of a CPU Unit that
does not have F1 marked near the DIP
switch, contact your OMRON representa-
tive.