Group 3.2: Start/Stop Setup - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Application
Code
Parameter
P3.1.2.5 Motor preheat function
Motor preheat tempe-
P3.1.2.6
rature limit
P3.1.2.7 Motor preheat current
P3.1.2.9 U/f ratio selection
P3.1.2.15 Over-voltage controller
Under-voltage control-
P3.1.2.16
ler
P3.1.2.17 StatorVoltAdjust
P3.1.2.18 Energy optimization
P3.1.2.19 Flying Start Options
3.5.4

Group 3.2: Start/Stop setup

Start/Stop commands are given differently depending on the control place.
Auto control place (I/O A): Start, stop and reverse commands are controlled by 2 digital inputs chosen
with parameters P3.5.1.1 and P3.5.1.2. The functionality/logic for these inputs is then selected with pa-
rameter P3.2.6 (in this group).
24-hour support +1-800-877-7545 (Dial 2)
Table 25: Advanced motor settings.
Min
Max
Unit
0
3
-20
80
°C
0.5*I
0
A
L
0
1
0
1
0
1
50.0%
150.0%
0
1
0
1
Siemens Industry, Inc. • 35
Default
ID
0 = Not used
1 = Always in stop state
2 = Controlled by DI
0
1225
3 = Temp limit (heat sink)
NOTE: Virtual digital input
can be activated by Real
Time Clock
Motor preheat is switched
on when the heat sink tem-
perature goes below this
level (if par. P3.1.2.5 is set
to Temperature limit.
0
1226
If limit is e.g. 10 °C (50 °F)
feeding current starts at 10
°C and stops at 11 °C
(51.8°)
(1 °C (1.8 °F) hysteresis).
DC current for pre-heating
of motor and drive in stop
Varies
1227
state. Activated by digital
input or by temperature
limit.
Type of U/f curve between
zero frequency and the field
Varies
108
weakening point.
0 = Linear
1 = Squared
0 = Disabled
1
607
1 = Enabled
0 = Disabled
1
608
1 = Enabled
Parameter for adjusting sta-
100.0
659
tor voltage in permanent
magnet motors.
The drive searches for the
minimum motor current in
order to save energy and to
lower the motor noise. This
0
666
function can be used for
example in fan and pump
applications
0 = Disabled
1 = Enabled
0 = Shaft direction is
searched in both
directions.
0
1590
1 = Shaft direction is only
searched in the same
direction as the frequency
reference
Description
3

Advertisement

Table of Contents
loading

Table of Contents