multiple times with different comments. Every acknowledgement is written to the internal memory
and is visible in the alarm log.

5.4.4.3. Alarms Config

Fig. 5.16: Menu Link settings > Alarms > Config
The diagnostics system of the link monitors the operation of both units.
It generates various event outputs - system warnings and alarms. The event is always written to the
system log and indicated in the status bar and Alarms/Status screen. Some events have adjustable
thresholds. Events with no adjustable thresholds may or may not be Enabled. If they are not Enabled,
the system event is not activated even if the system status is changed.
If the event goes above or below the set parameter limits or a link goes down or up, you can choose
to send an SNMP trap. All SNMP traps are OFF in defaults.
Alarms
Inside temperature [°C]
Default >80
Temperature inside the unit (on the modem board). Active if temperature exceeds the threshold.
Voltage min [V]
Default <40
Lower threshold of supply voltage. Active if voltage drops below min voltage threshold.
The same SNMP trap (same OID) applies for both Voltage min and max.