The manufacturer's instructions for installation and maintenance
shall be followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Appropriate cable, glands, and plugs need to be suitable for a
temperature of 5 °C greater than the maximum specified
temperature for location where installed.
4. The applicable temperature class, ambient temperature range and
process temperature range of the equipment is as follows:
5. Non-standard paint options (paint options other than Rosemount
Blue) may cause risk from electrostatic discharge. Avoid installation
that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth.
6. Display glass shall be positioned in such a way as to minimize the risk
of mechanical impact.
I7 IECEx Intrinsic Safety
Certificate
Standards
Markings
Voltage U
Current I
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. The Rosemount 4088 MV Transmitters fitted with transient
protection are not capable of withstanding the 500V test as defined
in Clause 6.3.13 of IEC 60079-11:2012. This must be taken into
account during installation.
Quick Start Guide
T4 for –50 ≤ T
≤ 80 °C with T process = –50 to 120 °C
a
T5 for –50 ≤ T
≤ 80 °C with T process = –50 to 80 °C
a
T6 for –50 ≤ T
≤ 65 °C with T process = –50 to 65 °C
a
IECEx BAS 13.0110X
IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIB T4 Ga (–60 ≤ T
Supply
22 V
i
147 mA
i
1 W
0
i
0
i
≤ +70 °C)
a
Modbus
RTD
9 V
15.51 V
26 mA
20.89 mA
1 W
80.94 mW
0
0
0
0
Quick Start Guide
33