Sunny Mini Central 6000A - SMA SUNNY MINI CENTRAL 4600A Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY MINI CENTRAL 4600A:
Table of Contents

Advertisement

SMA Solar Technology AG
11.1.3 Sunny Mini Central 6000A
DC Input
Maximum DC power at cos φ = 1
Maximum input voltage*
MPP voltage range
Rated input voltage
Minimum input voltage
Start input voltage
Maximum input current
Maximum input current per string
Number of independent MPP inputs
Strings per MPP input
* The maximum open‑circuit voltage that can occur with ‒10°C cell temperature may not exceed the maximum input voltage.
AC Output
Rated power at 230 V, 50 Hz
Maximum apparent AC power
Rated grid voltage
Nominal AC voltage
AC voltage range
Nominal AC current at 230 V
Nominal AC current at 240 V
Maximum output current
Total harmonic factor of the output current with
AC voltage < 2% and
AC power > 50% of rated power
Rated power frequency
AC power frequency
Operating range at AC power frequency 50 Hz
Operating range at AC power frequency 60 Hz
Displacement power factor, adjustable*
Power factor at nominal AC power**
Feed‑in phases
Connection phases
Overvoltage category according to
IEC 60664‑1
* Applies to SMC 6000A-11
** Applies to SMC 6000A/SMC 6000A-IT
Installation Manual
6 300 W
600 V
246 V ... 480 V
246 V
211 V
300 V
26 A
26 A
1
4
6 000 W
6 000 VA
230 V
220 V/230 V/240 V
160 V ... 265 V
26 A
25 A
26 A
≤ 3%
50 Hz
50 Hz/60 Hz
44 Hz ... 55 Hz
54 Hz ... 65 Hz
0.8
... 0.8
overexcited
underexcited
1
1
1
III
SMC46-60A-IA-IEN120471
Technical Data
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny mini central 5000aSunny mini central 6000a

Table of Contents