11 Technical Data
11.1 Sunny Mini Central 6000TL
DC Input
Maximum DC power at cos ϕ = 1
Maximum DC voltage *
MPP voltage range
DC nominal voltage
Minimum DC voltage
Start voltage, adjustable
Maximum input current
Number of MPP trackers
Maximum number of parallel strings
Voltage ripple of input voltage
Internal consumption during operation
* The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, may not exceed the maximum input voltage.
AC Output
AC nominal power at 230 V AC, 50 Hz
Maximum AC apparent power
Nominal AC current
Maximum output current
Maximum fuse protection
Harmonic distortion of output current at
AC T
voltage < 2 %,
HD
AC power > 0.5 AC nominal power
Nominal AC voltage
AC voltage range
AC grid frequency
Operating range at AC grid frequency
Power factor at nominal AC power
Supply phases
Connection phases
Overvoltage category as per
AUS/NZS 60950.1:2003
Overvoltage category as per EN 50178:1998
74
SMC6-8TL-IEN101040
P
DC
U
DC max
U
PV
U
DC nom
U
DC min
U
PV Start
I
PV max
U
pp
P
AC nom
S
AC max
I
AC nom
I
AC max
K
IAC
U
220 V / 230 V / 240 V
AC nom
U
AC
f
AC nom
f
50 Hz: 45.5 Hz ... 54.5 Hz
AC
60 Hz: 55.5 Hz ... 64.5 Hz
cos ϕ
SMA Solar Technology AG
6,200 W
700 V
333 V ... 500 V
350 V
330 V
400 V
19.0 A
1
4
< 10 %
< 10 W
6,000 W
6,000 VA
27 A
27 A
50 A
< 3 %
180 V ... 260 V
50 Hz / 60 Hz
1
1
1
II
III