Functional Specifications - Emerson Rosemount 1208C Reference Manual

Level and flow transmitter
Hide thumbs Also See for Rosemount 1208C:
Table of Contents

Advertisement

Reference Manual
00809-0200-7062
A.2 

Functional specifications

A.2.1 
General
Field of application
Continuous measurement of level and open channel flow.
Minimum dielectric constant
2
Measurement principle
Frequency Modulated Continuous Wave (FMCW)
Frequency range
77 to 81 GHz
Maximum output power
3 dBm (2 mW)
Internal power consumption
< 0.8 W in normal operation
Humidity
0 - 100% relative humidity, non-condensing
Turn-on time
< 60 s
A.2.2 
4-20 mA HART
Output
Two-wire, 4-20 mA. Digital process variable is superimposed on 4-20 mA signal, and
available to any host that conforms to the HART protocol. The digital HART
be used in multidrop mode.
HART universal revision
7
(3)
Time from when power is applied to the transmitter until performance is within specifications.
Reference Manual
(3)
®
Specifications and reference data
March 2023
signal can
®
69