Vertiv™ Liebert® EXM2 UPS User Manual
5 .3.3 O perato r Co ntro ls
The Operator login confers control of UPS functions:
Silence (Alarm)
Inverter On
Inverter Off
Reset Fault
Energy Saving Mode Activation
Battery Operations
Each command is available under the OPERATE menu. The OPERATE menu may be used by logging in with Operator,
Administrator and Service access.
N O T E: R isk o f im pro per o peratio n . Can cau se lo ad dro p resu ltin g in equ ipm en t dam age. T h e In verter
O n , In verter O ff, R eset F au lt an d En ergy Savin g M o de A ctivatio n co m m an ds will be available wh en ever
th e UP S is o peratin g. B efo re execu tin g an y co m m an d, verify th at th e UP S statu s is su itable fo r th e
co m m an d to be perfo rm ed.
O perate M en u Co m m an ds
All Operator commands are available from the OPERATE menu. The menu is available whenever the UPS has input power.
The UPS need not be supplying power to the load for the menu to be available. The animated mimic is not linked to data in
this view—touching a component will not cause it to display data.
F igu re 5.16 O P ER A T E m en u — O perato r lo gin
70
5 Operator Control and Display Panel