Parameter
Active power threshold of
grid during battery
discharge
Adjustment deadband
Automatic SOC
calibration
b. Set the battery working mode to TOU.
Description
Control the maximum target grid power when the grid-connection
point has zero power.
Allowed fluctuation of the target grid power for the grid-connection
point
•
Enable: Automatic SOC calibration is enabled. If the total charge
and discharge energy reaches the threshold or the calibration
function has not been triggered for 30 days, the SOC automatic
calibration is performed in battery racks. During calibration, the
cut-off SOC settings will be ineffective and the response of the
charge/discharge power may be impacted temporarily.
•
Disable: Automatic SOC calibration is disabled.
44