Installing Auxiliary AC Power Cables (with External Grid
5.6
Power Supply)
Installing Single-Phase AC Input Power Cables (Without External
5.7
Grid Power Supply)
•
If a UPS or other reliable backup power supply is used, perform the following steps to
connect single-phase AC input power cables.
•
Recommended UPS input switch specifications: 230/400 V AC 32 A/2P.
1. Remove the short-circuiting bar from 1–2 and insert it to 2–3 on the XU terminal block.
2. Remove the short-circuiting bar from 4–5 and insert it to 5–6 on the XU terminal block.
3. Connect the cables.
30