Changing HMI password
4.1.7.
18
Voltage Relay
Operator's Manual - ANSI Version
6. To store the new password and return the display to the view mode, press
. The display confirms the storage by flashing "- - -" once on the
display.
Alternatively, to exit the setting mode without storing the password
change, press
once before confirming and the display returns to the
view mode.
7. Press
to return the display to the idle mode.
Group Menu
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
U NOMINAL
PASSWORD HMI
TIME
TRIP CIRCUIT SUP

SPA password

The password for SPA bus communication is required for altering parameter
values via the SPA bus. The default password is 001. You can change the SPA
password either via the HMI or the SPA bus by first entering the currently
valid password into parameter V160 and then entering the new password into
parameter V161.
Change the SPA password as follows:
1. Press an arrow button to access the main menu
2. Use the arrow buttons to select CONFIGURATION\COMMUNICATION
\SPA SETTINGS\PASSWORD SPA and press
3. Press
to enter the setting mode and give the current HMI password if
required. If the default password 001 is still valid, no password is required.
4. The first digit of the password to be edited starts to flash. Set the digit
using
and
.
5. Activate the next digit to be set by pressing
Parameter Menu
CONFIGURATION
Scroll for the digit
PASSWORD HMI
:999
Set the digit
.
or
.
1MRS755971
Confirm
Cancel
A051583