How To Change Settings - ABB REU 610 Operator's Manual

Voltage protection relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755770
4.2.2.2.
Voltage Protection Relay
Operator's Manual
The views are used for reading and setting parameters, which are divided into two
main groups:
SETTINGS
*
CONFIGURATION
*

How to change settings

The actual settings consist of the settings of group 1 or group 2, depending on which
group has been selected to be active (indicated by an asterisk "*"). The actual
settings can be seen in the first parameter menu, for example:
SETTINGS\PROTECT. STAGES\ U> Un:0.00
Submenu
PROTECT. STAGES
U>
Un:0.00
Fig. 4.2.2.2.-1
Setting parameters in setting group 1 and setting group 2
By switching between setting groups 1 and 2, you can activate a whole group of
settings at the same time. Switch between the setting groups as follows:
With the parameter GROUP 1/GROUP 2 under the main menu group
*
SETTINGS.
With a digital input signal, provided that SGB1...5/4 has been set to 1 in both
*
setting groups (GRP1 and GRP2).
With parameter V150 via the SPA bus.
*
When a large number of settings is to be altered, for example during
the commissioning of the relay systems, use a PC equipped with the
necessary software.
If no PC is available, or when only a few settings are to be altered:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select the main menu group SETTINGS and the wanted
group menu (for example PROTECT. STAGES), and press
3. Use
or
to select the parameter to be changed and press
to select setting group 1 or 2 (GRP1 or GRP2). The active setting
4. Use
or
group is indicated by an asterisk "*".
5. Enter the setting mode by pressing
default password 999 is still valid, no password is required.
Parameter Menu
PROTECT. STAGES
* GRP 1
:0.00
GRP 2
:0.00
and give the password if required. If the
REU 610
REU 610
Confirm
Cancel
A051471
.
.
31