Detachable Plug-In Unit; Identifying The Product - ABB REU 610 Operator's Manual

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
4.4.
4.4.1.
44
Voltage Relay
Operator's Manual - ANSI Version
Table 4.3.2.3.-2
Warning codes (Continued)
Fault
DNP 3.0 configuration
error
DNP 3.0 module faulty
Checksum:
a)
The external fault warning can be routed to SO2 with SGF1/8.

Detachable plug-in unit

Identifying the product

You can find the order number on a label under the lower handle of the relay.
When checking the order number of the relay plug-in unit, be
careful not to lift the handle more than 25º (approx. 40 mm).
Lifting the handle any further detaches the plug-in unit from the
case.
a
y
Fig. 4.4.1.-1
Checking the order number of the relay
α = 25º
y = 40 mm
Weight
Description
value
16
DNP 3.0 configuration error
DNP 3.0 parameters should be formatted
*
and re-configured
32
Faulty memory in DNP 3.0 card or
communication lost between DNP 3.0 card
and relay
The DNP 3.0 card or plug-in unit requires
*
service
63
1MRS755971
A040165