Submenu; Hmi Password - ABB REU 610 Operator's Manual

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755971
4.1.5.
4.1.6.
Voltage Relay
Operator's Manual - ANSI Version

Submenu

The menu structure contains several subgroups. The name of the main menu
group is always shown on the first line. The second line displays either the
name of the group menu, the name of the parameter and the parameter value,
or just the parameter value, in which case it is also the name of the parameter.
MEASUREMENTS
Uab
VT x 0.00
Fig. 4.1.5.-1
Display showing the first submenu
Enter a submenu by pressing
*
Navigate between the main levels in the submenus by using
*
Press
to return the display to the idle mode.
*

HMI password

The HMI password protects all user-changeable values on the technical level
from being changed by an unauthorized person. The password function
remains inactive until the default password is replaced. The default HMI
password is 999. You can also change the password from a remote unit via
parameter V162, but you can only read the password via the HMI.
As soon as you have replaced the default HMI password, the new password is
required for altering parameter values. Once you have given the valid
password, the display remains in the setting mode until returned to the idle
mode.
SETTINGS
PASSWORD
Fig. 4.1.6.-1
Password request for editing setting parameters
Change the HMI password as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select CONFIGURATION\PASSWORD HMI and
press
.
3. Press
to enter the setting mode and give the current HMI password if
required. If the default password 999 is still valid, no password is required.
4. The first digit of the password to be edited starts to flash. Set the digit
using
and
.
5. Activate the next digit to be set by pressing
; exit by pressing
:000
or
REU 610
A051587
.
or
.
A040230
.
17