Relay Mismatch
A "Relay Mismatch" message indicates that there is a difference between the types of one or
more relays in the configuration for the Power Control Processor Mk2 and the types of relays
detected in the panel. This condition occurs when relays have been added or altered in the
panel after configuration.
To resolve a "Relay Mismatch" condition, reconfigure the panel using the Quick Rack Setup
menu. See
Quick Rack Setup on page 21
Relay Removed
A "Relay Removed" message indicates that one or more relays are missing from the panel,
according to the configuration of the Power Control Processor Mk2.
This condition occurs when relays have been removed from the panel after configuration. To
resolve a "Relay Removed" condition, reconfigure the panel using the Quick Rack Setup menu
(see
Quick Rack Setup on page 21
electrical safety procedures.
When a relay has not been removed from the panel and the condition persists, additional
troubleshooting is required with power removed.
Breaker Mismatch
A "Breaker Mismatch" message only applies to Sensor IQ panels. "Breaker Mismatch"
indicates that there is a difference between the types of one or more breakers in the
configuration and the types of breakers detected in the panel. This condition occurs when
breakers have been added or altered in the panel after configuration. To resolve a "Breaker
Mismatch" condition, reconfigure the panel using the Quick Rack Setup menu. See
Rack Setup on page 21
Breaker Removed
A "Breaker Removed" message only applies to Sensor IQ panels. "Breaker Removed" indicates
that one or more breakers are missing from the Sensor IQ panel, according to the
configuration of the Power Control Processor Mk2. This condition occurs when breakers have
been removed from the panel after configuration. To resolve a "Breaker Removed" condition,
reconfigure the panel using the Quick Rack Setup menu (see
replace the breaker in the panel following appropriate electrical safety procedures.
When a breaker has not been removed from the panel and the condition persists, additional
troubleshooting is required with power removed. For information on how to replace a breaker,
see the Sensor IQ Installation Manual .
Breaker Error
A "Breaker Error" message only applies to Sensor IQ panels. "Breaker Error" indicates that the
control boards are unable to communicate with a circuit breaker.
Perform the following steps to resolve a "Breaker Error":
45
.
) or replace the relay in the panel following appropriate
.
Quick Rack Setup on page 21
Power Control Processor Mk2 Configuration Manual
Quick
) or
Need help?
Do you have a question about the Power Control Processor Mk2 and is the answer not in the manual?
Questions and answers