Gas Valve Calibration - Ferroli KONA 12 Operating Instructions Manual

Low nox
Hide thumbs Also See for KONA 12:
Table of Contents

Advertisement

Available languages

Available languages

KONA
A. Gas conversion from G31 to G30, from Propane to Butane and
vice versa (from G30 to G31, from Butane to Propane)
For the KONA LPG model, which will be factory set to G31 (Propane), to
convert it to G30 (Butane) just set the parameter "FA",
which in this example would be as follows:
Model:
From the factory value, for G31 (Propane)
to the new value,
for G30 (Butane)
according to the liters of the water heater model, as indicated in the table
of parameters (see Section 3.5.1). To convert from G30 to G31, still
for the KONA LPG model, the procedure would be the same up to this
point, modifying the parameter FA with the corresponding value.
B. Gas conversion with conversion kit
If the gas conversion was done by converting the water heater, it is
necessary to set first also the parameter FA, according to the gas to
be used by the KONA water heater:
Model:
Conversion to G20
G31, Propane
Conversion to LPG
G30, Butane
Conversion to G25
Conversion to G230
and according to the liters of the water heater model, as indicated in the
table of parameters (see Section 3.5.1).
In this case, after modifying the parameter FA, the gas valve must be cali-
brated using the parameters following FA.

5. Gas valve calibration

The gas valve must be calibrated for every conversion of gas in the
KONA water heater converted using the corresponding kit (i.e. for ev-
ery conversion except the LPG model which is convert-
ed from G31 to G30 and vice versa).
Therefore, follow the entire procedure in Section 3.1.2 to
carry out this operation correctly.
6. Confirm and exit parameters
To complete the parameter change procedure:
• Touch the "
" button until the symbol "qU" appears.
• Touch the Standby button to confirm and exit
The water heater returns to STANDBY status
7. Gas data plate positioning
After carrying out the conversion, apply the label for the new gas,
contained in the document bag, near the technical data plate.
3.1.2 Gas valve calibration
To be done only in the following cases :
- GAS VALVE REPLACEMENT
- ELECTRONIC BOARD REPLACEMENT
- GAS CHANGE WITH CONVERSION
The gas valve (with integrated modulating actuator) is not mechanically
12 L
15 L
17 L
calibrated; the minimum and maximum flow rate is electronically adjusted
2
7
12
by 2 parameters:
3
8
13
GAS VALVE CALIBRATION
1 Check that the supply pressure, according to the
2 In the same Technical Data table, check the water
12 L
15 L
17 L
1
6
11
2
7
12
3
8
13
3 Connect a pressure gauge to check the gas valve outlet
4
9
14
5
10
15
4 Set the water heater to STANDBY with the Standby button
5 Activate the list of parameters by pressing the ECO button
6 Touch the Standby button, the first parameter "FA" ap-
7 By touching the "
8 Selecting "PH", it is necessary to touch the Standby
9 To set the parameter "PH", touch the "
10 To set the next parameter to be calibrated, starting from
11 Selecting "P2", it is necessary to touch the Standby
A73023750 - Rev. 01 - 02-2023
Par.
Description
PH
Total maximum pressure (entire burner)
P2
Minimum pressure (burner minimum section)
type of gas, corresponds to that indicated in the
Technical Data table (see Section 4.3).
heater maximum and minimum pressure values
according to the model and type of gas, for con-
sidering in the following phases.
pressure.
.
for 5 seconds until "PP" appears on the display.
pears.
" button again, the first parameter
"PH", relevant to the Maximum Pressure of the valve to be
calibrated, appears .
button to access calibration, displaying the relevant internal
value of the Maximum pressure parameter.
on the panel until the pressure gauge indicates the Maxi-
mum nominal pressure minus 1 mbar. Wait 10 seconds for
the pressure to stabilize. If the pressure gauge indicates a
value different from the maximum nominal pressure, gradu-
ally increase the parameter "PH" with the "
each change, wait 10 seconds for the pressure to stabilize. If
the pressure gauge shows the same value as the Maximum
nominal pressure, confirm it with the Standby button.
"PH" it is necessary to touch the "
parameter "P2", relevant to the Minimum pressure.
button to access calibration, displaying the relevant internal
value of the Minimum pressure parameter.
Range
20 - F0
20 - F0
" or "
" button
" button. After
" button until reaching
71