7.4. Parameterization data
This paragraph includes list and explanation of relevant available parameters for IL transducer, listed according to IO-Link specification
• Predefined parameters - System
Index
Subindex
Object name
0x0002
0x00
System Command
U=User, M=Maintenance, S=Specialist
Table 3
System command values-
Access
Value
Command
U
M
S
0x01
W
W
W
ParamUploadStart
0x02
W
W
W
ParamUploadEnd
0x03
W
W
W
ParamDownloadStart
0x04
W
W
W
ParamDownloadEnd
0x05
W
W
W
ParamDownloadStore
0x06
W
W
W
ParamBreak
0x41
-
W
W
TeachSP1
0x42
-
W
W
TeachSP2
0xA0
-
W
W
Autozero
0xA1
-
W
W
ResetAutozero
0xA2
-
W
W
RelayThresholdConfirmation*
0xA4
-
W
W
ResetPressureMaxValue
0xA6
-
W
W
ResetPressurePeaksCounter
0xA7
-
W
W
ResetTemperatureMaxValue***
0xA9
-
W
W
ResetTemperaturePeaksCounter***
0xAA
-
W
W
ResetOperatingTimeCounters
0x82
-
W
W
RestoreFactorySettings
U=User, M=Maintenance, S=Specialist, - : command not available
*Available only in SIL 2 / PL d Relay output version
** Available only in SIL 2 / PL d Analog output version
*** Available only in T integrated version
Table 4
Autozero command application limits-
Transducer FS
FS ≤ 35 bar (500psi)
36 bar ≤ FS ≤ 199 bar (3000psi)
200 bar ≤ FS ≤ 349 bar (5000psi)
FS ≥ 350 bar
According to the different FS, the Autozero command can be applied only if the offset is within the percentage allowed by Table 4.
80618_MAN_IO-LINK IMPACT_12-2019_ENG
Access
Length
Data Type
U
M
S
W
W
W
1
Uint8
Data Type Description
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Percentage limit for autozero application [%FS]
100%
40%
20%
10%
Value (example)
See Table 3
It allows to teach "Setpoint 1" (SP1) for the selected Switching Signal Chan-
nel(s). SP1 is defined by one "TeachPoint" ("Single value teach-in" mode)
It allows to teach "Setpoint 2" (SP2) for the selected Switching Signal Chan-
nel(s). SP2 is defined by one "TeachPoint" ("Single value teach-in" mode)
Set to zero the offset of transducer (see limits in Table 4)
Reset the Autozero effect command
Confirm the change of value of the Relay Threshold
Reset the Peak of pressure measured from last power on
Reset the Counter of peaks of pressure (stored in EEprom)
Reset the Peak of temperature measured from last power on
Reset the Counter of peaks of temperature (stored in EEprom)
Reset the Time counter and Time in pressure counter
Recall the settings stored during factory calibration
Description
15