Emerson FB3000 Instruction Manual page 66

Remote terminal unit
Hide thumbs Also See for FB3000:
Table of Contents

Advertisement

Emerson FB3000 RTU Instruction Manual
D301851X012
October 2022
2. Select the HART channel you want to configure; there are four HART channels per module.
3. If this channel is an analog input, click the Configuration tab to configure the AI.
4. Specify whether this is a Primary or Secondary HART Master in the HART Master Type field
5. Enable the Termination Resistor if required.
6. Choose the HART Comm Mode
7. Click Save. If you chose Multidrop, the HART menu creates a button for each of the
8. Click on the Device button to configure the HART device on this channel.
9. Select the variables you want to poll from the device, then click Save and Close the screen.
10. If this channel uses multi-drop, repeat steps 8 and 9 for any unconfigured devices.
56
If you have a single HART device on the channel, select Point to Point.
If multiple devices are multi-dropped on the channel, select Multidrop and specify the
Number of Devices.
devices.