2.2.11 "Diagnosis" submenu
This menu displays the current values of busload (%), voltage (V), current (mA)
and temperature (°C).
The busload is a measure for the number of telegrams in a certain period of time.
100 % busload is reached at approx. 50 telegrams per second (Group Value Write
telegrams with 1 byte). The voltage shows the current value of the bus voltage, the
current the sum of bus and auxiliary current. The temperature is measured in the
device.
2.2.12 "History" submenu
The history shows the value range (min. and max.) for busload (%), voltage (V), current (mA) and
temperature (°C) of the last 24 hours.
Pressing button down
following values: Busload, voltage, current and temperature. The time span of each graph is
approx. 2 minutes.
To return to the main menu, press button escape button ❻.
2.2.13 "Bus Reset" submenu
In this submenu, the KNX line can be reset. By pressing button enter
switched off. The maximum reset time is 30 seconds. This time can be shortened by pressing
button escape ❻.