Individual addressed telegrams
Individual addressed telegrams are used when downloading devices.
The following settings are possible:
Block
No individual addressed telegram is forwarded to KNX.
Route
All individual addressed telegrams are forwarded to KNX.
Filter
The individual address is used to check whether the received individual addressed telegram
is forwarded to KNX.
The "Route" setting should only be used for test purposes.
Broadcast telegrams
Broadcast telegrams are used when assigning individual addresses.
The following settings are possible:
Block
No received broadcast telegram is forwarded to KNX.
Route
All received broadcast telegrams are forwarded to KNX.
Repetition of group telegrams
The following settings are possible:
Disabled
The received group telegram is not repeated on KNX in case of error.
Enabled
The received group telegram is repeated up to three times in case of error.
Repetition of individual addressed telegrams
The following settings are possible:
Disabled
The received individual addressed telegram is not repeated on KNX in case of error.
Enabled
The received individual addressed telegram is repeated up to three times in case of error.
Repetition of broadcast telegrams
The following settings are possible:
Disabled
The received broadcast telegram is not repeated on KNX in case of error.
Enabled
The received broadcast telegram is repeated up to three times in case of error.