Group telegrams (main groups 14 to 31)
The main groups 14 to 31 form the extended group address range of the ETS.
The following settings are possible:
Block
No group telegram of the main groups 14 to 31 is forwarded to IP.
Route
All group telegrams of the main groups 14 to 31 are forwarded to IP regardless of the filter
table.
Filter
Here it is checked by means of the filter table whether the received group telegram is
forwarded to IP.
The "Route" setting should only be used for test purposes.
Individual addressed telegrams
Individual addressed telegrams are used when downloading devices.
The following settings are possible:
Block
No individual addressed telegram is forwarded to IP.
Route
All individual addressed telegrams are forwarded to IP.
Filter
The individual address is used to check whether the received individual addressed telegram
is forwarded to IP.
The "Route" setting should only be used for test purposes.
Broadcast telegrams
Broadcast telegrams are used when assigning individual addresses.
The following settings are possible:
Block
No received broadcast telegram is forwarded to IP.
Route
All received broadcast telegrams are forwarded to IP.
Acknowledgement (ACK) of group telegrams
The following settings are possible:
Always
An acknowledge is always generated for received group telegrams (from KNX).
Only if routed
For received group telegrams (from KNX), an acknowledge is only generated when
forwarding to IP.