Local settings via the menu
By deactivating this option, it is no longer possible to make settings via the device menu. This
concerns the setting of the IP configuration, the resetting of the counters, the device reset, the bus
reset and the temporary changing of the filter settings.
Manual operation on device
The duration of the manual operation mode is set here. For commissioning or test purposes, the
filter table can be temporarily bypassed. This can be set under the "Filter" menu item. When
terminated, the normal operating mode, as programmed, is automatically executed again.
The following configuration options are available:
▪
Disabled
▪
Enabled with time limit 1 min
▪
Enabled with time limit 10 min
▪
Enabled with time limit 30 min
▪
Enabled without time limit
8.7 Routing (KNX -> IP)
Group telegrams (main groups 0 to 13)
The main groups 0 to 13 form the standard group address range of the ETS.
The following settings are possible:
▪
Block
No group telegram of the main groups 0 to 13 is forwarded to IP.
▪
Route
All group telegrams of the main groups 0 to 13 are forwarded to IP regardless of the filter
table.
▪
Filter
Here it is checked by means of the filter table whether the received group telegram is
forwarded to IP.
The "Route" setting should only be used for test purposes.