9 Disconnecting the Inverter from Voltage Sources
8.
Danger to life due to electric shock when touching exposed DC
conductors or DC plug contacts if the DC connectors are damaged or
loose
The DC connectors can break or become damaged, become free of the DC cables, or no
longer be connected correctly if the DC connectors are released and disconnected
incorrectly. This can result in the DC conductors or DC plug contacts being exposed.
Touching live DC conductors or DC plug connectors will result in death or serious injury due
to electric shock.
• Wear insulated gloves and use insulated tools when working on the DC connectors.
• Ensure that the DC connectors are in perfect condition and that none of the DC
conductors or DC plug contacts are exposed.
• Carefully release and remove the DC connectors as described in the following.
9. Release and remove the DC connectors. To do so,
insert a flat-blade screwdriver or an angled
screwdriver (blade width: 3.5 mm) into one of the
side slots and pull the DC connectors out. When
doing so, do not lever the DC connectors out, but
insert the tool into one of the side slots only to
release the locking mechanism, and do not pull on
the cable.
10. Ensure that the DC connectors on the product and those that are equipped with DC
conductors are in perfect condition and that none of the DC conductors or DC plug contacts
are exposed.
11. Ensure that no voltage is present at the DC inputs on
the inverter using a suitable measuring device.
12. Unscrew (TX25) all 10 screws of the enclosure lid of
the AC-Connection Unit and remove the enclosure
lid carefully towards the front.
13. Set the screws and the enclosure lid aside and store safely.
92
STP50-4x-BE-en-23
DANGER
2
A
B
C
SMA Solar Technology AG
1
< 3 0 V
10x
Operating manual