12 Decommissioning the Inverter
13. When the DC surge arresters are inserted, pull the
surge arresters out of the slots. To do so, squeeze
the grooved areas on the left and right sides of the
surge arrester.
14. Position the enclosure lid of the DC-Connection Unit
on the DC-Connection Unit and first tighten the
upper-left and lower-right screws, and then the
remaining screws crosswise (TX 25, torque: 6 Nm).
15. Screw all four transport handles as far as they will
go into the taps on the right- and left-hand side until
they lie flush with the enclosure. When doing so,
ensure that the transport handles are screwed into
the tapped holes so that they are perfectly straight.
If the transport handles are not screwed in straight,
this can make it more difficult or even impossible to
unscrew them later on and can damage the tapped
holes to the extent that transport handles can no
longer be screwed into them.
16. Insert a screwdriver into the holes in the transport
handle and turn the screwdriver through 90°. This
ensures that the transport handles are securely
tightened.
17. To remove the feet or profile rails, lay the inverter carefully on the AC-Connection Unit side.
18. To pack the inverter: pack the inverter in its original packaging. To do this, place the lower
part of the original packaging with padding on the pallet. Then place the inverter on the pallet
with the padding. In doing so, place the AC connection unit side of the inverter on top of the
padding.
118
STP50-4x-BE-en-23
SMA Solar Technology AG
_
+
_
+
1
2
10x
10x
1
2
90°
Operating manual
1
4x
4x