Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
This manual contains important instructions that should be followed during installation of your Liebert NXL UPS.Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
Page 8
Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. Vertiv | Liebert NXL 250-400 Installation Manual...
NOTICE Three-phase input supply required. The standard Liebert NXL UPS is suitable for connection to three-phase, four-wire (+ Earth) TN-C, TN-S, IT-G, IT-IG or, three-phase, three-wire plus ground, IT-UG. If using with IT Power system, a 4-pole disconnect device must be included as part of building installation.
(see Environmental Parameters in Table 10). The Liebert NXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings.
1.4.2 Clearances The Liebert NXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened.
When bringing the 1+N system online for the first time or after removing one unit, Vertiv recommends checking the bypass current mismatch. To check the bypass current mismatch: Place a load on the bypass of each UPS module.
Single-Module and Multi-Module Mechanical Installation Figure 1 Cabinet arrangement—Liebert NXL single-module, battery cabinets, maintenance bypass cabinet Applicable to: Liebert 250 - 400 kVA 480V, 250 - 300 kVA 575/600V except without Maintenance Bypass Cabinet The side panels and Note: If a maintenance bypass...
Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed. External overcurrent protection must be provided. See Table 10 - Liebert NXL UPS specifications for overload capacity. Dual Input When wiring the UPS with a separate rectifier and bypass input, each input must be protected separately.
• AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields. 2.2.1 Sizing the Input Breaker Feeding a Liebert NXL UPS The rectifier nominal input current value (Table 11) is based on providing enough power to operate the inverter at full rated load when the input voltage is nominal.
Page 16
For control connection details, see 2.3 - Control Cable and Communication. NOTE If fault bracing brackets were removed during installation, they MUST be replaced. 6. Close and secure the interior and exterior doors. Vertiv | Liebert NXL 250-400 Installation Manual...
Kick plates must be installed. If the unit is to be installed in a position that does not permit access to rear kick plates, then kick plates must be installed before the unit is placed in its final position. Vertiv | Liebert NXL 250-400 Installation Manual...
TB1154A TB0813 TB0819 EXTERNA L INT BATT EXT BATT STATUS BYP CNTL TB0812 TB0825 TB0817 RECT REPO CNTL BATT MTR TB1156 LBS VO LTAGE TB0818 TB0820 TB0826 REPO TB0824 CNTRLN STATUS FORM C Vertiv | Liebert NXL 250-400 Installation Manual...
For 1+N systems with a maintenance Bypass, these Aux contacts must be run to each module from an isolated source. 2. For 1+N systems, these breaker Aux contact go to the UPS that it is associated with. Key Status Input can be either Form-C, N.O. or N.C. contact. Vertiv | Liebert NXL 250-400 Installation Manual...
Care must be taken to prevent the drain wire from touching any other component in the module. 8. Attach control wires to the side of the control door where the Inter-Module Board (IMC) is attached. Do not run wires across the IMC board. Vertiv | Liebert NXL 250-400 Installation Manual...
6. Attach the control wire to the side of the control door where the Inter-Module Board (IMC) is attached. Do not run wires across the IMC board. Figure 7 Inter-Module Communication Board wiring diagram—Digital LBS P3108 P3108 P3108 02-806730-xx 02-806730-xx 02-806730-xx P3109 P3109 P3109 UPS 3 UPS 1 UPS 2 Vertiv | Liebert NXL 250-400 Installation Manual...
Failure to set the ground fault interrupters properly could cause loss of power to the critical load. 2.5.3 Preferred Grounding Configuration, Battery Systems Open-rack battery systems, depending on local code requirements and customer preference, are normally: • Floating (ungrounded) • Center-tapped and floating Vertiv | Liebert NXL 250-400 Installation Manual...
For Multi-Module systems using a 3-wire bypass, the Neutral-Ground bond must be made at the common neutral connection point in the switchgear or parallel cabinet. 2.5.5 High Resistance Ground Systems The Liebert NXL is compatible with High Resistance Ground Systems. See your local Vertiv representative for details. ROUNDING...
3.1.3 Load Bus Synch An optional Load Bus Synch (LBS) system can be used to synchronize two Liebert NXL UPSs or an Liebert NXL UPS to a Liebert Series 610 UPS. 3.1.4 Remote Alarm Panel The remote alarm panel has LED alarm lights.
4. Press up to four (4) events. Selected events will show up under Relay 1 Assignment. NOTE To deselect an event, click on the event. Repeat Steps 3 and 4 for each relay. 6. Press SAVE to keep the settings. Vertiv | Liebert NXL 250-400 Installation Manual...
• Delay, sec—0 to 99.9 (default: 0) 3.2.3 Input Contact Isolator Board The Input Contact Isolator Board (ICI) provides a Liebert NXL module interface for up to eight external user alarm or message inputs to be routed through the NXL’s alarm network. The eight contacts are normally open dry contacts.
All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit. Signal voltage: 100mA @ 12VDC. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. Vertiv | Liebert NXL 250-400 Installation Manual...
4. Rectifier Input Power (Phases A-B-C) 5. Output Power (Phases A-B-C) 6. Output Neutral 7. Ground The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars. Vertiv | Liebert NXL 250-400 Installation Manual...
4.) Bypass Input Power (Phases A-B-C) 5.) Bypass Neutral 6.) DC Power 7.) Ground The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars. Vertiv | Liebert NXL 250-400 Installation Manual...
Low-voltage cables can be installed through the top of each unit. The entry conduit landing plate is shipped inverted. To install, remove conduit plate, flip and reinstall. Removal of side plate is for access to pull wires. Vertiv | Liebert NXL 250-400 Installation Manual...
The UPS will operate at full load, but the battery charge will either be reduced or off (depending on input current). ** The UPS will operate at full load, but UPS may source share with the batteries (depending on input current). *** UPS will be in Battery mode Vertiv | Liebert NXL 250-400 Installation Manual...
Page 49
/ 328 rise between 4921-9842 (100m rise between 1500-3000m) Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. 2. Depth dimensions include the front door and rear panel. Vertiv | Liebert NXL 250-400 Installation Manual...
For units with an input transformer, the Rectifier Input Feed Breaker must be set to handle the Liebert NXL transformer inrush of up to eight times the nominal current. 4. For breaker coordination while the module is overloaded, see the current- versus-time values on the overload curves, Figures 34 and 35.
(# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per UPS Rating conduit Copper Conductors Aluminum Conductors (2) 2C 2-600kcmil, #1/0AWG (2) 2.5C 2-750kcmil, #3/0AWG (2) 2.5C 2-750kcmil, #1/0AWG (3) 2.0C 2-500kcmil, #3/0AWG Vertiv | Liebert NXL 250-400 Installation Manual...
Page 52
2. For continuous operations not at 86°F (30°C), recommend that the site planner choose the appropriate cable type based on the particular installation requirements. Conduit size is based on FMC type conduit with two neutral conductors rated at 200% of phase. Vertiv | Liebert NXL 250-400 Installation Manual...