Table 3-5: Frequency/Digital Outputs possible configurations
Frequency/Digital output
Frequency /Digital Output
3
(2)
(1)
Solid blue line denotes valid selection for Frequency/Digital Output 1.
(2)
Black dashed-line denotes valid selections for Frequency/Digital Output 2 and
Frequency/Digital Output 3.
Output for FODO1 and Digital Output1 (Group 1 on the CPU Module) share a
common ground and have 50 V isolation. FODO2 and FODO3 (Group 2 on the CPU
Module) share a common ground and have 50 V isolation. This allows an output to
be connected to a different flow computer. The outputs are opto-isolated from
the CPU Module and have a withstand voltage of at least 500 V rms dielectric.
Figure 3-6: CPU Module - Frequency/Digital inputs common ground
A. FODO1 and Digital input1 - shared common ground (Group 1)
B. FODO2 and FODO3 - shared common ground (Group 2)
3.6.2 
Analog input settings
The The 960-24
Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These analog input
signals are configured to sink. The two independent analog input circuits are
configured for conventional 4-20 mA service. Also, 24 VDC isolated power supply
connection is provided for an external power source. Refer to the Field wiring
diagram DMC-004936 in
Installation manual
Frequency output 2A
Frequency output 2B
Digital output 2A
Digital output 2B
MSTS has the capability to sample analog temperature (Analog
Engineering
Source configuration
Drawings.
Electrical Installation