Electrical connection
9.3 System integration
Terminal
Shaft
Cable entry
box type
height
(power)
1XB7700-
SH225
3 x M75 x 1.5
P02
and
SH280
1XB7712-
SH225
4 x M75 x 1.5
P03
and
SH280
1)
M16 x 1.5 thread arranged at 90° angle to signal connection; thread only with options A12, A25 and encoder version A
(without encoder)
Depending on the version of metric cable gland (based on the MOTION-CONNECT cable type and cable glands from HUGRO
2)
or from AGRO)
Current-carrying capacity based on EN 60204-1 and IEC 60364-5-52, routing type E
3)
M16 x 1.5 thread arranged opposite to the signal connection (lateral to the cable entry plate); thread only for option A12 and
4)
encoder version A (without encoder)
Note
Terminal box type 1XB7700-P02
For cable entry, 3 cable glands can only be fit in if cable glands from AGRO or HUGRO are used.
Cable glands from Pflitsch or Lapp, for example, are larger and it is not possible to fit 3 of them
into the available space.
Terminal box design
Figure 9-7
232
Cable entry
(external sig‐
nals)
1 x M16 x 1.5
4)
1 x M16 x 1.5
4)
Terminal screw M5
Grounding screw M5
Insulation strips
Terminal box gk803, 3-pole (SH 80)
Outer cable di‐
Number of main ter‐
ameter, max.
minals
mm
2)
68
Phases: 3 x 2 x M12
Grounding: 3 x
clamping plate
68
Phases: 3 x 4 x M16
Grounding: 4 x M16
Configuration Manual, 12/2022, A5E51895839A
Max. cross-
Max.
section
current
per
per
terminal
terminal
mm
A
2
3)
3 x 150
700
4 x 185
1150
1PH8 SIMOTICS M main motors