11.
In conjunction with Viessmann heat pumps.
In order for the Smart Grid function of a Viess-
mann heat pump to be used via EEBUS, the heat
pump parameters must be set accordingly: Set
"Enable Smart Grid 7E80" to "3".
Service instructions of the "Vitotronic 200,
type WO1C"
12.
In conjunction with Viessmann heat pumps.
In order for the heat pump to provide sufficient
flexibility for the energy management system, the
set value boosts for Smart Grid must be set
accordingly.
Service instructions of the "Vitotronic 200,
type WO1C", chapter "Parameters for
Smart Grid"
Note
The energy and performance data of the heat
pump transmitted to the energy management sys-
tem via EEBUS are calculated values. These may
differ from the actual values and values measured
with an energy meter, and are therefore not suita-
ble for billing purposes.
(cont.)
EEBUS and ripple control receiver
If a ripple control receiver is to be used in parallel to
the EEBUS interface with an energy management sys-
tem, it must be connected to the cross connect PCB
via the heat pump's "power-OFF" function. The "Smart
Grid" function via the heat pump's cross connect PCB
or the EA1 extension is not possible in this case.
Heat pump installation and service instructions
Commissioning
23