Service and maintenance
7.2 Safety instructions for hazardous areas
7.2.3
Opening the device in energized state
Opening the device in energized state
Danger of explosion in hazardous areas.
• Only open the device in a de-energized state.
• Check prior to startup that the cover, cover locks, and cable inlets are assembled in
Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in
energized state in hazardous areas.
Open enclosure
Danger of explosion in hazardous areas as a result of hot components and/or charged
capacitors inside the device.
Follow these steps when you open the device in a hazardous area:
1. Disconnect the device from the power supply.
2. Make sure you observe the wait time listed on the warning label before you open the device.
3. Carry out a visual check of the sensor inlet and outlet.
Exception: Devices with "Intrinsic safety Ex i" explosion protection type only may also be
opened in an energized state in hazardous areas.
Maintenance during ongoing operation in a hazardous area
There is a danger of explosion when carrying out repairs and maintenance on the device in a
hazardous area.
• Isolate the device from power.
• Alternatively: Make sure that the atmosphere is explosion-free (hot work permit).
• Wait 10 minutes after disconnecting the power supply before you open all doors and covers.