APPENDIX 3
Table A-6 shows the items that can be monitored in operation mode. The output sig-
nal levels for multi-function analog outputs shown in the table are for a gain of 100.0
and a bias of 0.00.
Table A-6 Constants Monitored in Operation Mode
Con-
Func-
stant
Name
tion
No.
DC bus voltage
U1-02
U1 02
DC Bus Voltage
AC power supply voltage
U1-04
U1 04
AC Voltage
Current at power side
U1 05
U1-05
AC Current
Power at power side
U1 07
U1-07
AC Power
AC power supply
frequency
U1-08
U1-08
AC Frequency
Input terminal status
U1-10
U1 10
Input Term Sts
Status
Output terminal status
Monitor
U1-11
U1 11
Output Term Sts
Operation status
U1-12
U1 12
Int Ct1 Sts 1
Cumulative operation
time
U1-13
U1-13
Elapsed Time
Software No.
U1-14
U1 14
FLASH ID
CONSTANTS LIST
Monitors the DC voltage of the power regenerative unit s
Monitors the DC voltage of the power regenerative unit's
internal main circuit
Monitors the AC power supply voltage.
Monitors the AC power supply voltage
Monitors the AC current at power side.
Monitors the AC current at power side
Monitors the AC power supply at power side
Monitors the AC power supply at power side.
Monitors the AC power supply frequency.
Monitors the AC power supply frequency.
Shows input ON/OFF status.
00000000
U1-10 =
*1 : Can be selected by user constant H1-01 or H1-02.
Shows output ON/OFF status.
00000000
U1-11 =
*2 : Can be selected by user constant H2-02 or H2-03.
Powerregenerativeunitoperatingstatus
00000000
U1-12 =
Monitors the power regenerative unit's elapsed operating
time.
time.
Can be set with user constants o2-07 or o2-08.
(Manufacturer's ID number)
(Manufacturer's ID number)
Function
1 : MANUAL RUN (terminal S1) ON
1 : AUTO RUN (terminal S2) ON
1 : AUTO RUN (terminal S2) ON
1 : EXFLT (terminal S3) ON *1
1 : RESET (terminal S4) ON *1
1 : Not used. (always 0)
0 : Not used. (always 0)
1 : Multi-function output 1
(terminals M1-M2) ON *2
(terminals M1-M2) ON *2
1 : Multi-function output 2
(terminals M3-M4) ON *2
0 : Not used. (always 0)
1 : Fault output
(terminal MA/MB-MC) ON
1 : Running
0 : Not used. (always 0)
1 : Reset input ON
O
0 : Not used. (always 0)
1 : Power regenerative unit ready
0 : Minor fault detected
1 : Major fault detected

APPENDIX 3 CONSTANTS LIST

Output Signal Level for
Min.
Multi-function
Unit
Analog Outputs
200 V class : 400 V/10 V
400 V class : 800 V/10 V
400 V class : 800 V/10 V
1 V
1 V
(0 to +10 V Output)
200 V class : 200 V/5 V
400 V class : 400 V/5 V
400 V class : 400 V/5 V
1 V
1 V
(0 to +10 V Output)
Rated current /10 V
Rated current /10 V
1 A
1 A
(0 to +10 V Output)
Rated power /10 V
Rated power /10 V
1 kW
1 kW
(0 to +10 V Output)
60 Hz /10 V
0.01
(0 to +10 V Output)
(0 to +10 V Output)
Hz
Hz
(Cannot be output)