Configuring The F-Do Signal Module - Siemens SIMATIC 317TF-2 DP Getting Started

Automation system s7-300
Table of Contents

Advertisement

Step
Activity
7
Deactivate the remaining channels of the 1Vs / 3VS supply group and all channels of the 2VS / 4VS supply
group by clearing the check marks of the "Activated" option.
Confirm the entries with OK.
8
Enter a password for the safety program.
Result
The configuration of the F-DI signal module is complete.
4.3

Configuring the F-DO signal module

Use of the fail-safe output channels
Configure a fail-safe F-DO signal module. The table below shows which channels are used
and the meaning of the connected lights.
Table 4- 2
Channel
DO channel 0
DO channel 1
DO channel 2
DO channel 3
Note
You have to enter the password for the safety program to configure the fail-safe module.
The names and order of the parameters may differ from the following description if you are
using a different fail-safe module. You can find information on the parameters in the online
help.
CPU 317TF-2 DP: Controlling a SINAMICS S120 with Safety Functions
Getting Started, 07/2010, A5E02982990-01
Use of the output channels
Use
Safety mode deactivated
Setup mode activated (safety door open and key switch on "Setup")
Emergency off active (emergency stop button is pressed or safety door
open without setup mode)
Acknowledgment required (at least one F-I/O has a fault requiring
acknowledgment or needs to be reintegrated)
4.3 Configuring the F-DO signal module
Configuration
23