Configuring The F-Di Signal Module - Siemens SIMATIC 317TF-2 DP Getting Started

Automation system s7-300
Table of Contents

Advertisement

Configuration

4.2 Configuring the F-DI signal module

Step
Activity
3
Select the following settings in the fields:
CPU type: CPU317TF-2 DP
"Generate Technology System Data" option activated
"MPI/DP": New, type "MPI", transmission rate 1.5 Mbit/s or higher
"PG/PC": New, "Assign" option activated
If required, press the button "Help" to obtain additional information. Confirm with "OK".
Result: A new SIMATIC 300 station is created in the project with a CPU 317TF-2 DP (latest version).
4
Open the hardware configuration and add the following modules, as specified in the section "Requirements
(Page 7)":
Digital input module DI16xDC24V, e.g. 6ES7321-1BH02-0AA0
Digital output module DO16xDC24V/0.5A, e.g. 6ES7322-1BH01-0AA0
5
Save and compile the hardware configuration.
The system compiles your project, and adds the "Technology Objects" object to the project window in
SIMATIC Manager.
6
Download the hardware configuration to the target system.
4.2
Configuring the F-DI signal module
Use of the fail-safe input channels
Configure a fail-safe F-DI signal module. The following table shows which safety elements
need to be connected to the individual channels and how the channels need to be
configured.
Note
You must set a password to provide access permission for the safety program.
Table 4- 1
Channel
0 and 12
1 and 13
2 and 14
3
5
20
Configuration of the input channels, supply group 1Vs / 3Vs
Use
1. of the safety door, 2-
channel
2. of the safety door, 2-
channel
Emergency stop
switch, 2-channel
Key switch for setup
mode, single-channel
Acknowledgment
button, single-channel
Parameter
Evaluation of encoder
Type of encoder interconnection
Evaluation of encoder
Type of encoder interconnection
Evaluation of encoder
Type of encoder interconnection
Evaluation of encoder
Type of encoder interconnection
Evaluation of encoder
Type of encoder interconnection
CPU 317TF-2 DP: Controlling a SINAMICS S120 with Safety Functions
Value
1oo2 evaluation
2-channel equivalent
1oo2 evaluation
2-channel equivalent
1oo2 evaluation
2-channel equivalent
1oo1 evaluation
Single-channel
1oo1 evaluation
Single-channel
Getting Started, 07/2010, A5E02982990-01